Case Study: Low Oil Level Fault Alarm
Fault Description
The transformer issued a low oil level fault alarm, prompting the customer to contact VE Power for help.
Fault Analysis
1. Our field technicians were dispatched to the site to investigate.
• The oil level gauge was confirmed to be functioning properly, and no evidence of oil leakage was observed.
2. During the fault event, the feeder protection relay also indicated a ground fault, suggesting the transformer may have experienced an internal fault to ground.
3. A Dissolved Gas Analysis (DGA) was performed, and results showed elevated gas levels, consistent with internal electrical faults.
Site Activities & Findings:
Electrical diagnostic testing was conducted, including:
• Winding Resistance Test (WRT)
• Transformer Turns Ratio (TTR)
• Polarization Index (PI)
The test results indicated that the H1–H3 winding was exhibiting a ground fault condition.
Recommendations & Coordination
Following consultation with the transformer manufacturer, it was determined that the transformer should be replaced.
Corrective Actions Taken:
- Our team performed a full transformer replacement.
- We reconnected all instrumentation and verified proper operation.
- Final electrical acceptance testing was completed per NETA standards to confirm the replacement unit’s integrity.